2016年6月12日星期日

1.Fixed gas detector SI-100 with display screen

chinacoal11
http://www.chinacoalintl.com/
http://m.chinacoalintl.com/
http://china-machinary.com/
we provide service of enterprise's customs declaration, inspection.
Device description
SI-100 is a fixed gas detector installed in a place where potential gas hazard exists to measure oxygen, toxic gas and combustible gas. It shows not only the concentration of gas but also diagnostic result of the unit itself through the LCD display and can be connected to the controller with a standard 4-20mA analog output communication or RS-485 digital communication.
Major Applications
Steelworks, petrochemical, refining, shipbuilding, wastewater treatment plants and septic, mining, power, agency, chaengkeu, confined space work area
Features
01. SI-100 measures the concentration of the flammable gas, toxic gas, oxygen and display with LCD
02. Easy magnetic bar operation
03. Big digital LCD installed with a blue backlight
04. Explosive proof structure
05. Water/dust proof structure
06. Simple gas calibration
07. RUSSIA Gost-R Certification
08. EUROPE electromagnetic waves fitness Certification
Specification
Model
SI-100
Measuring gas
CH4
O2
CO, H2S, SO2, NH3
H2
Measuring type
Diffusion Type
Measuring method
Catalytic
Galvanic
Electrochemical cell
Electrochemical cell
Measuring range
0~100%LEL
0~30%VOL
CO : 0~500ppm,
H2S : 0~100ppm,
SO2 : 0~20ppm,
NH3 : 0~100ppm
0~1,000ppm
Sensor life time
> 2 years
> 18Month
> 2 year
> 2 year
Measuring method
< 15sec/90%scale
< 15sec/90%scale
< 30sec/90%scale
< 30sec/90%scale
Accuracy
±3%/Full scale
Resolution
1%LEL
0.1%VOL
1PPM
1PPM
Parameter Control
Front 3 magnetic switch(calibration, maintenance, alarm setting)
Operation mode display
Digital LCD display, LCD Backlight, 4 Indicator LED
Measuring value display
Digital LCD Display(4-digit)
Alarm display
Visual : LCD alarm display, LCD Backlight, Indicator LED
Alarm output signal
Relay contact(Max 30Vdc, 5A) when Alarm occurred
Alarm level set
Programmable within dectection range
Output signal
Analog : 4-20mA, Digital : RS-485(Option)
PC interace
RS_485(Option)
Cable/Distance
Power + Signal cable : 3-wire 1.5sq(AWG16)/2,500m max,
RS-485 data communication cable : 1 pair(UL2919 RS-485)/1,200m max
Conduit connection
NPT 3/4" (2way)
Mounting type
Wall mount
Program set mode
"Alarm value(1,2,3 alarm)
Alarm time(instant&delay)1~30min
Alarm dead band
Relay output on/off
Operating temperature
-20℃~50℃
Operating humidity
5% to 95% RH(Non-condensing)
Operating power
10~30Vdc 600mA
Materianl
Aluminium, Stainless steel(STS304)
LCD size
55(W) X 30(H) mm
Dimensions
135(W) × 164(H) × 110(D)mm
Weight
1.9kg
Approval
Ex d IIC T5 IP65(IECEx)